The Worcester Greenstar Camray range of High Efficiency Condensing Boilers have experienced probelms with baffle removal from the primary heat exchanger.  This is due in the main to lack of regular maintenance and if these appliances are neglected then the extraction of baffles, essential for cleaning and ensuring the flueways remain clear, can be problematic due to the build-up of sulphur (a by-product of the combustion process).   As a result of this, many Oil-Fired technicians are not prepared to work on these appliances unless a full service history is provided.
 
Baffles subject to this problem are extremely difficult to remove without assistance,.  If the build-up of sulphur is particularly bad it can be broken down by using a solution of baking powder or bi-carbonate of soda and water.  A solution of one teaspoon of either bases to 100 ml of hot water (approximately 50 degrees celcius) should be sufficient. The Engineer must wear sufficient eye and hand protection as although the bi-carbonate of soda solution is harmless, the solution that will come off with the baffles will contain condensate salts, soot and rust.  The baffles should be rinsed with clean warm water once removed.
 
Range Heating can provide a baffle-removal service with the price of this dependent on the condition of the boiler and evidence of recent service history. In addition, we are certified by Worcester Bosch in Advanced Fault Finding on Greenstar Oil Fired appliances.
 
 
 
 
 